TANK TENDER SYSTEM CHECKOUT FOR PRESSURE LEAKS

(When gauge does not register at correct inch level of fluid in tank)

 

A leak can occur in three places within the Tank Tender System:

 

The following simple procedure will allow to quickly isolate a pressure leak within the system:

 

Notes

  1. The end of the nylon tube of the TPF should be cut off 1" above the tank bottom-if the end of the tube is jammed into the tank bottom, the instrument will not read accurately. The TPF should be installed over the deepest part of the tank with the tube hanging straight down to within 1" of the tank bottom. Tube should hang straight and not be curled, bent or blocked.
  2. If the gauge needle does not fall back to zero when all buttons are released or sticks at some level above zero, then the gauge may be over presurized or has been pumped over the red capacity line. In some cases, the gauge may be recalibrated (call for instructions) but in more extreme cases a new gauge may be needed. Causes of over pressurization: a) reading taken with deck fill pipe full (extra liquid in fill pipe plus full tank may exceed gauge capacity), b) kink or blockage in nylon tubing run between instrument and TPF (no air can pass), c) blockage in TPF tube inside tank (no air can pass). It is better to have excess capacity on gauge than be at full capacity with a full tank. If a reoccuring problem, go to a larger gauge.
  3. If the gauge has been disconnected from the instrument panel, a new flat gasket might be neede at the T-fitting. If system is leaking, check this flat gasket.
  4. If tubing has been disconnected from legris connectors, always cut 1/4" off of the tubing end and push back into legris connector firmly, untill a click is felt and heard. If nylon tubing is not completely pushed into legris connector, the system will leak at this point.
  5. To test pump, cover the open port on the valve closest to the pump and pump (one stroke). If pessure holds at whatever level pumped to, then the pump is functioning accurately. (There is only one open port in the valve assembly).
  6. If there is an existing electrical system in the tank, remove before installing TPF.
  7. Fluid lying in nylon tubing between unit and tank will cause erratic readings; taking readings with deck fill pipe full can force fluid up into nylon tubing. Do not test with deck pipe full. Disconnect tubing at both ends and purge line clear.

 


[Home][ Back ]


Progress - Seaview
Z.I. Capitou
85 Rue Louis Lépine

83600 - Fréjus

FRANCE

E-Mail : info@seavieweurope.com      Phone: +33 (0)4 94 53 27 70     Fax: +33 (0)4 94 53 26 62